Manual Pdf Best — Xmtg-2000 Temperature Controller
Corrects long-term steady-state errors by adding up historical deviations. Derivative Time
Since the XMTG-2000 is often a generic rebrand of standard Chinese PID controllers (often sharing similarities with the XMT series or other "two-step" controllers), the exact PDF can sometimes be hard to find on a manufacturer's main website. xmtg-2000 temperature controller manual pdf
To enter the system parameter menu, press and hold the button for 3 seconds. Use the arrow keys to input the access password (typically 0001 or 0088 depending on firmware variant) if prompted. Press SET to cycle through these fundamental parameters: Parameter Name Description Default / Range Sn Input Sensor Type Selects the sensor (e.g., 0 = K, 2 = Pt100). Factory Variable P Proportional Band Adjusts proportional control. 0 turns unit to On/Off mode. 0.0 - 100.0% I Integral Time Eliminates steady-state offset error. 1 - 3600 sec D Derivative Time Responds to rapid temperature fluctuations. 0 - 3600 sec T Control Period Use the arrow keys to input the access
Solution: Test continuity on the sensor leads. Double-check your sensor specification and align it with the Sn parameter. 0 turns unit to On/Off mode
Thermocouples (K, J, E, S, T) and RTDs (Pt100, Cu50).
The parameter lock ( LCK ) stops unauthorized changes to your system configuration. LCK = 00 : All parameters are open for modification. LCK = 01 : Only the primary Set Value (SV) can be adjusted. LCK = 11 : All internal menus are completely locked. Step-by-Step Auto-Tuning Guide
This is the most requested section of the . Here is how to program your unit, assuming you have a typical relay or SSR output model.